Aienginear · Calculator v4.0.0

Vessel Volume & Calibration Calculator

1Vessel

Include head straight flanges in T/T.
+ = right end higher
From left tangent line

2Heads

3Liquid level and fluid

For hold-up times

4Level settings (% of height)

Percent of total internal height from the level datum. Draw-off = outlet nozzle top; liquid below it is dead (unpumpable) volume.

5API 521 fire case

Same length unit
1.0 = bare vessel
API 521 commonly 7.6 m (25 ft); same length unit

6Strapping table

Up to 5,000 rows. Fixed-length steps suit dip-stick and radar-gauge tables.

Aienginear report

Input summary

Aienginear figure

Vessel sketch at current level

Not to scale where heads are very shallow. Drawn by Aienginear.aienginear.com/vessel-volume-calculator/

Aienginear table

Volume and area breakdown

PartDescriptionDepth / lengthVolumeInternal surface

Aienginear table

Level settings, hold-up and surge times

Setting% heightLevelVolumeFill %Hold-up from setting belowTime at flow

Aienginear table

Wetted area and API 521 fire heat input

Q = 43,200·F·A0.82 W with adequate drainage and fire-fighting, or 70,900·F·A0.82 W without (API 521, SI form). A is the wetted area up to the lower of the liquid level and the fire-zone height. Confirm F, the fire-zone height and any credit for insulation against the edition of API 521 your project uses.

Aienginear solver

Volume to level (reverse calculation)

Enter a volume, a fill percentage or a mass to get the matching liquid level.

Aienginear chart

Calibration curve: volume against level

Aienginear table

Strapping (level-to-volume) table

Geometric calibration from internal dimensions. Generated by Aienginear Calculator v4.0.0.aienginear.com/vessel-volume-calculator/

Results are geometric values for design, level setting and estimating. Custody-transfer calibration needs physical measurement to API MPMS Chapter 2 / ISO 12917. Inputs stay in your browser. © Aienginear · aienginear.com