Tube Rupture Relief Valve Calculator | API 521 10/13 Rule & API 520 PSV Sizing

Reviewed against API Std 521, API Std 520 Part I & II, API Std 526 and ASME BPVC · Last updated 28 October 2026 · Calculator v5.0.0

Quick answer: For tube rupture relief valve sizing, a heat-exchanger tube rupture must be treated as a relief scenario when the low-pressure (LP) side design pressure is below 10/13 of the high-pressure (HP) side design pressure (API Std 521). The relief load is the flow through both open ends of one broken tube — an orifice of twice the tube’s internal area — from the HP operating pressure into the LP side at its relieving pressure. The relief device is then sized with API Std 520 Part I equations and an API Std 526 orifice letter is selected.

Key takeaways
  • The 10/13 ratio exists because ASME Section VIII Division 1 hydrotests at 1.3 × MAWP; an LP side rated at 10/13 of the HP side can survive full HP pressure without exceeding its test pressure.
  • Use the lowest design pressure of the LP side and every system it connects to (upstream and downstream), not just the exchanger shell.
  • The standard break model is a clean, double-ended guillotine break of a single tube close to the tubesheet.
  • Gas breaking into a liquid-full shell produces a fast pressure spike; API 521 recommends a transient analysis and a rupture disk is often the right device.
  • The free Aienginear suite below does the screening, relief load, PSV area and orifice selection, two-phase (omega and HEM) checks, transient analysis, rupture disk sizing and a printable report in one place.

Tube Rupture Relief Valve Calculator (API 521 / API 520)

Enter the HP (tube) side, LP (shell) side and tube geometry, then press Run Analysis. The suite screens the case with the 10/13 rule, calculates the relief load, sizes the PSV and selects the API 526 orifice. Further tabs cover the transient network solver, cubic equation-of-state properties, two-phase omega/HEM flow, rupture disk sizing and stress checks. Version 5.0.0 adds vendor Kb/Kw, rupture-disk Kc, the liquid viscosity factor Kv, a separate Z at relieving conditions, sub-critical PSV sizing, a choice of design or operating HP pressure for the leak flow, and a built-in self-test. Use Load Gas Example or Load Liquid Example to see a complete case, then open Report & Export to print or save the results.

Aienginear Tube Rupture Relief Valve Suite · v5.0.0Open full screen ↗

What is a tube rupture case?

In a shell-and-tube heat exchanger the two fluids are separated only by the tube wall and the tube-to-tubesheet joints. If one side runs at a much higher pressure than the other, a split tube, a failed joint or a vibration-fatigue crack lets the high-pressure fluid flow straight into the low-pressure side. When that inflow is larger than the LP side can pass through its normal outlets, its pressure rises — and if the LP side was never designed for the HP pressure, it can be overpressured within seconds.

API Std 521 treats the complete failure of one tube as the credible worst case for design. Smaller leaks are more likely in practice, but a relief system sized for a full break also covers them. The case applies to any exchanger with a large pressure difference: gas coolers on cooling water, high-pressure feed/effluent exchangers, steam heaters on low-pressure process lines and refrigerant chillers. For exchanger types and TEMA designations, see the heat exchanger guide.

Double-ended tube rupture in a shell-and-tube heat exchanger Schematic showing HP fluid escaping from both ends of a broken tube into the LP shell, with a PSV on the shell side. Break area = 2 × (π/4) · dᵢ² HP in HP out PSV / rupture disk on LP side LP shell side (design pressure Pₗₚ) HP tube side (design pressure Pₙₚ) © Aienginear.com
Figure 1 – Design-basis tube rupture: one tube breaks cleanly, so HP fluid enters the LP side from both open ends. Aienginear.com

The API 521 10/13 rule explained

API Std 521 allows the complete tube rupture case to be set aside when the LP side, including its upstream and downstream systems, has a design pressure of at least 10/13 of the HP side design pressure. The logic is simple: under ASME Section VIII Division 1 (UG-99) the LP side was hydrotested at roughly 1.3 × its design pressure. If 1.3 × PLP ≥ PHP, the LP side has already been shown to hold the full HP pressure without loss of containment, so no relief device is needed for this case.

Older equipment designed to codes that hydrotested at 1.5 × MAWP used a 2/3 ratio for the same reason. Some companies still apply 2/3 to legacy exchangers, but new designs follow 10/13.

Table 1 – Tube rupture screening outcomes (10/13 rule)Aienginear.com
HP design (barg)10/13 × HP (barg)LP design (barg)OutcomeAction
10076.930Credible caseSize relief device for full tube rupture
10076.975Credible, marginalCheck if raising LP design to ≥ 77 barg is cheaper than a relief system
10076.980ExemptConfirm connected piping and equipment are also ≥ 77 barg
4030.810Credible caseSize relief device; check liquid-full transient
1612.316ExemptSmall-leak and other scenarios still apply
Source: Aienginear calculation per API Std 521 screening logic.
Tube rupture decision flowchart Flowchart: compare LP design pressure with 10/13 of HP design; if lower, calculate relief load, check LP contents for transient risk, select PSV or rupture disk. Collect Pₙₚ and lowest Pₗₚ (incl. connected systems) Pₗₚ ≥ 10/13 · Pₙₚ ?(design pressures) Yes Full rupture exemptdocument & check leaks No Relief load: 2 tube ends, steady state LP side liquid-full? No PSV per API 520API 526 orifice Yes Transient analysisrupture disk often required © Aienginear.com
Figure 2 – Screening and device-selection logic used by the calculator. Aienginear.com

How to calculate the tube rupture relief load

The design basis is a sharp, double-ended break of one tube, usually assumed near the tubesheet. Fluid reaches the break from both directions, so the flow area is twice the internal cross-section of a single tube. The upstream pressure is the HP side at its maximum operating pressure (using design pressure is more conservative), and the downstream pressure is the LP side at its relieving pressure — set pressure plus allowable overpressure.

A_break = 2 × (π/4) × d_i² d_i = tube OD − 2 × wall Liquid (non-flashing): W = Cd · A · √(2 · ρ · ΔP) Gas, choked (P2/P1 ≤ r_c): W = Cd · A · P1 · √[ k·M/(Z·R·T) · (2/(k+1))^((k+1)/(k−1)) ] r_c = (2/(k+1))^(k/(k−1))

With high HP pressures the gas flow is almost always choked at the break, so the load depends only on the HP conditions. The compressibility factor matters at high pressure: methane at 91 bara and 40 °C has Z ≈ 0.87, which raises the calculated flow by about 7% compared with an ideal-gas estimate. The suite’s cubic equation-of-state engine (Peng–Robinson or SRK) evaluates Z, or you can enter a Z from your process simulator for mixtures. For general pipe-flow and gas property work, see the FlowStack Thermodynamic Suite.

The discharge coefficient is a choice, not a fixed value. A sharp-edged orifice typically has Cd around 0.6 for liquids; many companies use 0.6–0.7 for gases. A higher Cd gives a higher, more conservative relief load. Record the value you use in the relief study.

Table 2 – Common exchanger tube sizes and double-ended break areaAienginear.com
Tube ODBWGWall (mm)ID (mm)Break area, 2 ends (mm²)
5/8″ (15.88 mm)161.65112.57248.3
3/4″ (19.05 mm)161.65115.75389.6
3/4″ (19.05 mm)142.10814.83345.6
1″ (25.40 mm)142.10821.18704.9
1″ (25.40 mm)122.76919.86619.7
1¼″ (31.75 mm)142.10827.531,190.9
Calculated by Aienginear from nominal BWG wall thickness. Use the actual specified wall of your exchanger.

Tube rupture relief valve sizing with API 520 and API 526

Once the relief load is known, the LP-side device is sized at the LP relieving pressure. For a single valve on a non-fire case the allowable overpressure is 10% of set pressure (16% for multiple valves). The 21% fire allowance does not apply to tube rupture. The required effective area is compared with the standard orifice letters of API Std 526 and the next larger orifice is selected.

Gas, critical flow (API 520 Part I, SI): A [mm²] = W [kg/h] / (C · Kd · P1 [kPa a] · Kb · Kc) · √(T · Z / M) C = 0.03948 · √[ k · (2/(k+1))^((k+1)/(k−1)) ] Liquid (certified, 10% overpressure): A [mm²] = 11.78 · Q [L/min] / (Kd · Kw · Kc · Kv) · √( G / (P1 − P2) [kPa] )

Kd is the effective discharge coefficient (0.975 for gas and 0.65 for liquid when using API 526 effective areas). Kb and Kw correct for back pressure on balanced-bellows valves and must come from the manufacturer. Kc is 0.9 when an uncertified rupture disk sits ahead of the valve. Kv is the viscosity correction for liquids, found from the Reynolds number. After choosing the valve, check inlet loss (normally under 3% of set) and outlet back pressure per API Std 520 Part II; the pipe pressure drop calculator helps with the line checks.

Table 3 – API Std 526 standard effective orifice areasAienginear.com
LetterArea (in²)Area (mm²)LetterArea (in²)Area (mm²)
D0.11071.0L2.8531,840.6
E0.196126.5M3.602,322.6
F0.307198.1N4.342,800.0
G0.503324.5P6.384,116.1
H0.785506.5Q11.057,129.0
J1.287830.3R16.010,322.6
K1.8381,185.8T26.016,774.2
Effective areas for preliminary sizing. Actual (certified) areas and coefficients come from the valve manufacturer.

Two-phase and flashing tube rupture

Many real cases are not single-phase. A hot HP liquid can flash as it enters the LP side, and gas entering a liquid-filled shell first pushes liquid out through the relief device before vapour follows. Sizing these as all-liquid or all-gas can under-size the device. The suite’s Two-Phase / HEM tab applies the Leung omega method (API Std 520 Part I, Annex C) — you supply the mixture specific volume at the relieving pressure and at 90% of it, and it finds ω, the critical pressure ratio and the mass flux — and also a direct-integration homogeneous equilibrium model (HEM). For ω above about 4, or near the thermodynamic critical point, use a more rigorous method or a simulator. Separator and knock-out drum sizing downstream of the relief header can be checked with the two-phase separator sizing calculator.

Transient surge and choosing the relief device

A steady-state calculation assumes the LP side pressure rises slowly enough for the valve to open and pass the load. That is reasonable when the LP side contains gas, which acts as a cushion. When the LP side is full of liquid, the incoming high-pressure gas cannot be absorbed: a pressure wave travels through the shell and connected piping at sonic speed, and the peak can occur in milliseconds — faster than a spring-loaded valve can lift. API Std 521 therefore calls for a transient (dynamic) analysis where the pressure difference is large and the LP side is liquid-full. Rupture disks, which open in milliseconds, are the usual answer in those cases, sometimes in combination with a PSV. The suite’s Transient Network tab gives a first look at the pressure–time response before a full dynamic study.

Table 4 – Relief device selection for tube ruptureAienginear.com
SituationUsual deviceWhyWatch-outs
LP side gas/vapour, moderate ΔPSpring PSV (conventional or bellows)Gas volume damps the pressure riseBack pressure, inlet loss, JT cooling
LP side liquid-full, HP gasRupture disk (alone or ahead of PSV)Opens fast enough for the surgeTransient study, disk burst tolerance, Kc = 0.9
LP side liquid-full, HP liquidLiquid-trim PSV or rupture diskPressure wave is smaller than with gasCheck surge for long LP piping
Flashing HP liquidPSV sized two-phaseVapour generation raises the volume flowOmega validity, outlet line two-phase flow
LP design raised to ≥ 10/13 HPNo device for this caseCase eliminated by designAll connected systems must be raised too
Aienginear engineering guidance; confirm with your company relief philosophy.
Pressure ladder for the worked example Bar chart comparing HP design 100 barg, HP operating 90 barg, 10/13 threshold 76.9 barg, LP relieving 33 barg and LP design 30 barg. HP design100 HP operating90 10/13 × HP design76.9 LP relieving (110%)33.0 LP design / set30.0 Pressure, barg © Aienginear.com
Figure 3 – Worked example pressures: the LP design (30 barg) is far below the 76.9 barg threshold, so the tube rupture case governs. Aienginear.com

Worked examples

Example 1 – Methane cooler, gas into gas-filled shell

A gas cooler has methane in the tubes (design 100 barg, operating 90 barg, 40 °C) and an LP shell side designed for 30 barg. Tubes are 3/4″ OD, 14 BWG. A single conventional PSV is set at 30 barg with 10% overpressure and discharges to atmosphere.

Table 5 – Example 1 results (Aienginear worked calculation)Aienginear.com
StepQuantityResult
110/13 × 100 barg vs LP design 30 barg76.9 > 30 → case credible
2Tube ID / double-ended break area14.83 mm / 345.6 mm²
3LP relieving pressure (30 × 1.10 + 1.013)34.01 bara
4Pressure ratio vs critical ratio (k = 1.31)0.374 < 0.544 → choked
5Z at 91.0 bara, 40 °C (Peng–Robinson)0.867
6Relief load, Cd = 0.714,138 kg/h (31,169 lb/h)
7PSV area: C = 0.02641, Kd = 0.975, Z = 0.940 at 34 bara691.5 mm² (1.072 in²)
8API 526 orificeJ (830.3 mm²), 83% utilised

Expansion from 91 to 34 bara cools methane noticeably. If the cooled temperature is used for sizing, the required area increases; check the relieving temperature you use and confirm the LP side’s minimum design metal temperature.

The worked results use an ideal sharp-edged break (no friction along the tube). The suite can also include the friction of the broken-tube path, which lowers the flow slightly, so its results may differ a little from these tables.

Example 2 – Cooling water on the shell, HP water in the tubes

Treated water at 60 barg (design 65 barg, 992 kg/m³) flows in 3/4″ 14 BWG tubes. The shell side is rated 10 barg and normally liquid-full. A liquid-trim PSV is set at 10 barg.

Table 6 – Example 2 results (Aienginear worked calculation)Aienginear.com
QuantityResult
Screening: 10/13 × 65 = 50 barg vs 10 bargCase credible
ΔP across break (61.01 − 12.01 bara), Cd = 0.649.0 bar
Relief load73,614 kg/h (74.2 m³/h, 1,237 L/min)
PSV area (Kd 0.65, Kv ≈ 1.0)673.4 mm²
API 526 orificeJ, 81% utilised
Transient flagLiquid-full LP side – check surge

Common tube rupture sizing mistakes

  • Checking only the exchanger shell. The 10/13 test applies to the LP side and every system it can push into, including upstream equipment if a check valve can fail.
  • Using one tube end. The design basis is two open ends; one end halves the load.
  • Using 21% overpressure. That allowance is for fire only.
  • Ignoring Z at high pressure. Ideal-gas sizing under-predicts flow for most hydrocarbons above about 50 bar.
  • Assuming a PSV protects a liquid-full shell. Without a transient check, the valve may open too late.
  • Forgetting credit for normal outlets. API 521 allows credit for the LP side’s normal outlet flow only if it remains open and is not affected by the failure — document any credit taken.
  • Not revisiting the case. Rerating, new tube material or changed operating pressures can turn an exempt exchanger into a credible case. Include it in turnaround management-of-change reviews.

Standards and codes referenced

Table 7 – Standards used by this article and calculatorAienginear.com
StandardEdition reviewedUsed for
API Std 521 – Pressure-relieving and Depressuring Systems7th ed. 2020, incl. Errata 1 (2022)Tube rupture scenario, 10/13 rule, transient guidance
API Std 520 Part I – Sizing and Selection10th ed. 2020Gas, liquid and two-phase (omega) sizing equations
API Std 520 Part II – Installation7th ed. 2020Inlet loss and outlet back pressure checks
API Std 526 – Flanged Steel Pressure-relief ValvesCurrent editionStandard orifice letters and areas
ASME BPVC Section VIII Div. 1 & Section XIII2025 editionHydrotest basis (UG-99), overpressure protection rules
ISO 23251 / ISO 41262019 / current partsInternational equivalents for relief systems and devices
Always confirm the edition adopted in your project specification. Aienginear.com

Further reading: the API standards catalogue and API’s announcement for API Std 520 Part I.

Why use the Aienginear tube rupture calculator?

Table 8 – Feature comparison with typical free online toolsAienginear.com
FeatureAienginear suiteTypical free tool
API 521 10/13 exemption screening with decision logicYesOften missing
Real-gas properties (Peng–Robinson / SRK)YesIdeal gas or manual Z
Choked and sub-critical flow, gas and liquidYesUsually choked gas only
API 520 sizing with API 526 orifice selectionYesSeparate tool needed
Two-phase omega method and HEM integrationYesRare
Transient network solver and rupture disk sizingYesRare
Vendor Kb/Kw, Kc, Kv and sub-critical PSV sizingYesRare
SI / US units and printable report with exportYesRare
Built-in self-test of the calculation engineYesNo
Free, no login, runs in the browserYesVaries

The tool is a preliminary engineering and design-support calculator. It does not replace a full relief study, a dynamic simulation, or the valve manufacturer’s certified sizing.

Frequently asked questions

What is the 10/13 rule for heat exchanger tube rupture?

API Std 521 says a complete tube rupture need not be considered when the low-pressure side and its connected systems have a design pressure of at least 10/13 of the high-pressure side design pressure. The ratio comes from the 1.3 × hydrotest of ASME Section VIII Division 1.

Why is the tube rupture area twice the tube cross-section?

The design basis is a clean break of one tube. Fluid escapes from both broken ends, so the total flow area is two times the internal area of the tube.

Should I use operating or design pressure on the high-pressure side?

API 521 bases the leak flow on the HP side’s operating conditions; using the maximum operating pressure is common, and design pressure gives a more conservative result. State the basis in your relief study.

What overpressure applies to a tube rupture PSV?

Tube rupture is a non-fire case: 10% for a single relief device and 16% for multiple devices. The 21% allowance applies only to fire.

When is a rupture disk better than a relief valve for tube rupture?

When the LP side is liquid-full and the HP fluid is gas or flashing liquid, the pressure spike can be too fast for a spring valve. A rupture disk opens in milliseconds and is often selected after a transient analysis.

Does the calculator handle two-phase relief?

Yes. The Two-Phase / HEM tab applies the Leung omega method from API Std 520 Part I Annex C and a direct-integration HEM for flashing flow.

Is the Aienginear tube rupture calculator free?

Yes. It runs in your browser with no login, and the Report & Export tab prints or exports the inputs and results.

Can this tool replace HYSYS, a vendor sizing program or a relief study?

No. It is for screening and preliminary sizing. Final sizing must use project-specific fluid properties, certified valve data and, where needed, a dynamic simulation, reviewed by a qualified engineer.

Related Aienginear calculators and guides

PSV Relief Load Calculator

Fire, blocked outlet and other relief scenarios.

Heat Exchanger Sizing Calculator

Duty, LMTD and area for shell-and-tube units.

ASME VIII Pressure Vessel Calculator

Shell and head thickness, MAWP.

Hydrotest & Pressure Test Calculator

Test pressures behind the 10/13 rule.

Control Valve Sizing Calculator

Cv and choked-flow checks.

Fluid Flow & Pipe Sizing Calculator

Relief header and outlet line sizing.

Pressure Integrity & Safety Hub

All pressure-safety tools in one place.

All Engineering Calculators

Free process, piping and mechanical tools.

Disclaimer: This article and calculator are for education and preliminary engineering. Results must be verified by a qualified engineer using the governing code, the current editions of the referenced standards and manufacturer-certified data before use in design, procurement or operation.
Written by Muhammad Raza – founder of Aienginear and Head of Projects at an industrial EPC contractor, with 18+ years in oil & gas, petrochemical and power projects, turnarounds and shutdowns. About the author · Report an error or ask a question